Texas Senate · 90th Legislature, Regular Session
Official title: Relating to power duration requirements in emergency contingency plans adopted by end stage renal disease facilities.
Members who authored, joint-authored, or co-sponsored this bill.
SourceLegiScan (CC BY 4.0)90R
The bill changes the emergency contingency plan that an end stage renal disease facility (a dialysis facility) must adopt under Section 251.017(b), Health and Safety Code, unless the facility adopts a plan described by Subsection (d) or (e). Under current law, the plan must require an on-site fuel source with enough fuel to run the facility's emergency generator for at least 24 hours. The bill raises that to at least 72 hours, based on the electrical load demand on the generator for that period. The bill also gives the facility a second option, which is an on-site battery-powered generator with enough electrical capacity to power the facility for at least 72 hours. The existing exception in Subsection (c) still applies to this power requirement. The bill leaves unchanged the other plan requirements, including the generator standards, the 10-foot distance from the electrical transformer, the 24 hours of potable water on-site, and the water valve connection for an outside vendor. Each facility must change its plan as needed to comply no later than December 1, 2027, and the Act takes effect September 1, 2027. The bill does not state what the changes will cost; the fiscal note would cover that.
Read the full text below for the definitive meaning.
Each version links to the authoritative document on capitol.texas.gov.
90R3020 LRM-D By: Miles S.B. No. 320 A BILL TO BE ENTITLED AN ACT relating to power duration requirements in emergency contingency plans adopted by end stage renal disease facilities. BE IT ENACTED BY THE LEGISLATURE OF THE STATE OF TEXAS: SECTION 1. Section 251.017(b), Health and Safety Code, is amended to read as follows: (b) Unless the facility adopts a plan described by
Subsection (d) or (e), an end stage renal disease facility must adopt an emergency contingency plan as required by Subsection (a) under which the facility is required: (1) to have an on-site emergency generator that: (A) has a type 2 essential electrical distribution system in accordance with the National Fire Protection Association 99, Section 4.5, and the National Fire Protection Association 110; (B) is installed, tested, and maintained in accordance with the National Fire Protection Association 99, Section 4.5.4, and the National Fire Protection Association 110; and (C) is kept at all times not less than 10 feet from the electrical transformer; (2) except as provided by Subsection (c), to maintain : (A) an on-site fuel source with sufficient [ that contains enough ] fuel capacity to power the on-site generator for not less than 72 [ 24 ] hours, as determined by the electrical load demand on the emergency generator for that period; or (B) an on-site battery-powered generator with sufficient electrical capacity to power the facility for not less than 72 hours; (3) to maintain a sufficient quantity of potable water on-site to operate the facility's water treatment system for not less than 24 hours; and (4) to maintain a water valve connection that allows an outside vendor to provide potable water to operate the facility's water treatment system. SECTION 2. Not later than December 1, 2027, each end stage renal disease facility shall modify the facility's emergency contingency plan as necessary to comply with Section 251.017(b), Health and Safety Code, as amended by this Act. SECTION 3. This Act takes effect September 1, 2027.
Statewide figures for the subjects tagged on this bill, to explore on the Data map. They describe Texas — not this bill or its effects.
SourceU.S. Census Bureau (ACS) & CDC PLACESstatewide Data layer
Each subject links to other 90R bills tagged the same way.
Source
SourceTexas Legislative Council (capitol.texas.gov)90R
No recorded roll-call votes on this bill.
SourceLegiScan (CC BY 4.0)90R
No fiscal notes or analyses recorded for this bill.
SourceLegiScan (CC BY 4.0)official fiscal notes & analyses (TLC)
Perch never collects comments itself — it points you to the Legislature's own hearing schedule and official public-comment channels (ADR-0007).
Official hearings & comment (capitol.texas.gov) →SourceTexas Legislative Council (capitol.texas.gov)official bill text (capitol.texas.gov)